The Eaton 93E UPS has reached end-of-life status. Eaton will continue to provide services and replacement parts for the 93E. If you're looking for a new UPS, the 9355 UPS and the 93PM UPS are the replacement options.
20-60 kVA
208/220 Vac Three-phase
50/60 Hz
Double conversion online with Multi-Mode (High efficiency)
98% in high efficiency mode
Tower
Internal batteries up to 60 kVA
External batteries up to 400 kVA
20 kVA/16 kW
30 kVA/24 kW
40 kVA/32 kW
60 kVA/48 kW
208/120V, 4 wire
220/127V, 4 wire
+20% / -15% at 208V with 100% load without depleting battery
50/60 Hz (40 to 72 Hz)
> 0.99 typical
5% THD
208/220, 3/4 wire
±1% static, ±5% dynamic at 100% resistive load change, <20 ms response time
9 AH, sealed, lead-acid, maintenance free
20 kVA – 21 minutes
30 kVA – 12 minutes
40 kVA – 10 minutes
60 kVA – 5 minutes
ABM or float technology
21
138
12
84
12
128
6.6
77
53.5 in/1360 mm
20.9 in/530 mm
31.5 in/800 mm
1049.4 lbs/ 476 kg
74.9 in/1880 mm
23.6 in/600 mm
31.5 in/800 mm
1499.1 lbs/ 680 kg
Up to 98% on high-efficiency mode
Up to 92% on double-conversion
Automatic on overload or UPS failure
102-110% for 10 minutes
111-125% for 30 seconds
>/=126% for 150 milliseconds
>/=150% for 40 milliseconds
Short circuit conditions: current limit at 2.5x nominal FL current for 60 milliseconds.
102-110% for 10 minutes
111-125% for 30 seconds
>/=126% for 150 milliseconds
>/=150% for 40 milliseconds
Short circuit conditions: immediate transfer to bypass; then 115% continuous, with transient capability of 20x nominal for 10 milliseconds.
102-110% for 10 minutes
111-125% for 30 seconds
>/=125%: current limited at 125% for 30 seconds
Up to 98% on high-efficiency mode
Up to 92% on double-conversion
Automatic on overload or UPS failure
102–110% for 10 minutes
111–125% for 30 seconds
>/=126% for 150 milliseconds
>/=150% for 40 milliseconds
Short circuit conditions: current limit at 2.5x nominal FL current for 60 milliseconds.
102-110% for 10 minutes
111–125% for 30 seconds
>/=126% for 150 milliseconds
>/=150% for 40 milliseconds
Short-circuit conditions: immediate transfer to bypass; then 115% continuous, with transient capability of 20x nominal for 10 milliseconds.
102-110% for 10 minutes
111–125% for 30 seconds
>/=125%: current limited at 125% for 30 seconds
Graphical LCD with blue backlight
(4) LEDs for notice and alarm
Yes
(1) RS-232
(1) REPO
(2) Mini-slot communication bays
(3) Building inputs
0ºC (32ºF) to +30ºC (86ºF);
Batteries recommended max. +25ºC (77ºF)
-25ºC (-13ºF) to +55ºC (131ºF) without batteries
+15ºC (59ºF) to +25ºC (77ºF) with batteries
5-95%, non-condensing
<65 dBA at 1 meter (noise less room) typical
< 1500m at +30°C (86ºF)
EN55022/EN55024
IEC 62040-2
ISO 9001: 2000 and ISO 14001: 1996
UL, cUL